20 Minute Negative Pressure
|
|
Door Sizes
|
Min.
|
Max
|
|
Single Door (W x H)
|
-
|
4' x 9'
|
|
Door Pairs (W x H)
|
-
|
8' x 9'
|
|
Pairs must have fire treated stile.
|
|
Optional veneer banding must be requested.
|
|
Dimensional Restrictions
|
Min.
|
Max.
|
|
Stiles
|
4"
|
-
|
|
Top Rail
|
4"
|
-
|
|
Bottom Rail
|
6-5/8"
|
-
|
|
Center Rails & Mullions
|
3"
|
-
|
|
Raised Panel Width
|
6"
|
32"
|
|
Raised Panel Height
|
6"
|
85-1/8"
|
|
Raised Panel Area SqInches
|
|
1632 in2
|
|
Flat Panel Width
|
6 1/8
|
26
|
|
Flat Panel Height
|
9 3/8
|
52
|
|
Flat Panel Area Sq inches
|
|
1352
|
|
Glass Width
|
4"
|
26"
|
|
Glass Height
|
4"
|
40"
|
|
Glass Square Inches
|
-
|
1040 in²
|
|
Light to Lock Restriction
|
5"
|
-
|
|
Sticking Options
|
|
Ovolo, Ogee, Mission,
& Square
|
|
Panel Options
|
|
Raised, Flat, Step, & Rimband Step
|
|
Flat panel size=5/8; Raised panel size=1.25
|
|
Glass Options
|
|
Must be 1/4" rated glass (i.e. Wire)
|
|
Can be supplied as open for fire rated glass
by others.
|
|
Mandatory fire clips
|
|
Machining Restrictions
|
|
Must have positive latching hardware
|
|
No concealed vertical rod exit device
|
|
No double egress pairs
|
|
No raceways
|
|
Arched panel doors are allowed (A or L doors)
(No arch door are allowed- AA doors)
(No radius doors are allowed R or RR
doors)
|
|
Auto Door Bottom can be surface or
mortised
|
|
V-Groove on panels
|
|
Raised panels
|
Flat panels
|
|
Yes
|
Yes
|
|
Face molding is OK on
this
|
|
|
|
|
| Evaluated and in Compliance with the following Standards: |
| • UBC 7-2 (1994) Uniform Building Code Standard |
| • UL 10b (1997) Standard for Fire Test of Door Assemblies |
| • NFPA 252 (1999) Standard Methods for Fire Tests of Door Assemblies |
20-Min Positive |
20-Min Neutral |
45-Min Positive |
60-Min Positive |
90-Min Positive
|